Skip to content
EXC. VAT
INC. VAT
RCBO vs MCB at westbasedirect.com

RCBO's vs MCB's: Explained a few different ways...

An MCB protects the cable. An RCBO protects the cable and the person. That is the whole difference in one line, and everything else follows from it. An MCB trips on overload and short circuit. An RCBO does the same job and adds residual current detection, so it also disconnects when current is leaking to earth, which is what happens when someone touches something live.

The short answer

For almost every domestic circuit in a new UK consumer unit, the answer is RCBO. BS 7671 requires 30 mA RCD protection on socket outlets up to 32 A and on domestic lighting circuits, and Regulation 314.1 requires the installation to be divided so a single fault causes minimum inconvenience. A board full of RCBOs satisfies both. A board with two RCDs satisfies the first but not really the second, because one earth fault takes out half the house.

30 mA residual current rating required for additional protection BS 7671 Reg 411.3.3
32 A socket outlet rating at or below which RCD protection applies BS 7671 Reg 411.3.3
300 ms maximum operating time for a general non-delay RCD at rated residual current IET Wiring Matters
1 circuit lost when an RCBO trips, against half a board with a shared RCD BS 7671 Reg 314.1

Regulation numbers refer to BS 7671:2018+A2:2022, the IET Wiring Regulations. Sources are listed in full at the end of this article.

What each device actually does

Both devices sit on a DIN rail in your consumer unit and both will disconnect a circuit. They are watching for different things.

  MCB RCBO
Overload protection Yes Yes
Short circuit protection Yes Yes
Earth leakage detection No Yes
Additional protection against electric shock No Yes, at 30 mA
Needs a separate RCD upstream to meet BS 7671 Usually yes No
What trips if there is an earth fault The shared RCD, taking every circuit behind it That circuit only
Typical width in the board 1 module 1 to 2 modules
Cost per device Lower Higher
One correction worth making. You will sometimes read that RCBOs can be adjusted for sensitivity. Domestic RCBOs cannot. They are supplied with a fixed residual current rating, almost always 30 mA for additional protection. Adjustable sensitivity belongs to certain industrial RCDs and relays, not to the devices going into a house consumer unit.

Why RCBOs win in practice: Regulation 314.1

The strongest argument for RCBOs is not shock protection, because a split load board with RCDs provides that too. It is what happens to the rest of the house when something goes wrong.

BS 7671 Regulation 314.1 requires an installation to be divided into circuits so that a single fault causes the minimum inconvenience, and so that danger and inconvenience during inspection and testing are avoided. That sounds abstract until you look at a board.

Diagram comparing a consumer unit populated with individual RCBOs against a board using MCBs behind a shared RCCB
Left: every circuit on its own RCBO. Right: several MCBs sitting behind one shared RCCB. In the second arrangement, one earth fault anywhere disconnects every circuit on that RCD.

On the right hand arrangement, a faulty kettle can take out the lighting, the freezer and the alarm at the same time, in the dark, at three in the morning. On the left, only the socket circuit the kettle is on disconnects. That is the practical meaning of minimum inconvenience, and it is why RCBO boards have become the default specification for new domestic work rather than a premium option.

What an all RCBO board buys you
  • Fault isolation. One circuit trips, not half the board.
  • Faster diagnosis. The tripped device tells you which circuit is at fault immediately.
  • No cumulative leakage. Several circuits sharing one RCD add their standing earth leakage together, which is a common cause of unexplained tripping.
  • Simpler testing. Circuits can be tested individually without disconnecting others.
  • Room to grow. Adding a circuit does not mean rebalancing which RCD it sits behind.

What BS 7671 actually requires

Two requirements do most of the work in a domestic installation. The first is additional protection for socket outlets.

Socket-outlets with a rated current not exceeding 32 A in locations where they are liable to be used by persons of capability BA1, BA3 or children (BA2, BA3), and socket-outlets with a rated current not exceeding 32 A in other locations.

IET, Wiring Matters issue 91, summarising Regulation 411.3.3 of BS 7671. See the IET's Mythbusters article on 30 mA RCD protection for socket outlets.

There is a documented exception, and it is narrower than people assume. RCD protection can be omitted only for socket outlets in the second category, and only “where a suitably documented risk assessment undertaken with the involvement of a skilled person (electrically) determines that RCD protection is not necessary”. The IET is explicit that “the documented risk assessment shall be provided with the appropriate electrical installation certificate”. In a normal house that exception effectively does not apply.

The requirement also has a ceiling. It “does not apply to socket-outlets rated at more than 32 A. Neither is there a distinction between single and three-phase supplies.”

The second requirement is Regulation 411.3.4, added by Amendment 2, which brought AC final circuits supplying luminaires in domestic premises into scope for 30 mA additional protection. Between sockets and lighting, that is most of a house.

The Type A change most people missed

Buying an RCBO is no longer just a question of rating and curve. You also have to buy the right RCD type, and the old default is no longer acceptable for general domestic circuits.

Modern loads contain switch mode power supplies, LED drivers, inverters and EV chargers, all of which can put a small DC component into the residual current. A Type AC device cannot see that reliably. It can be desensitised by it and may operate late or not at all.

Type AC RCDs shall only be used to serve fixed equipment, where it is known that the load current contains no DC components.

IET, Wiring Matters, on Regulation 531.3.3 of BS 7671:2018+A2:2022. Type A is the minimum for general purpose domestic circuits incorporating socket outlets.
RCD type Detects Where it belongs
Type AC Sinusoidal AC residual current only Only fixed equipment where the load is known to contain no DC components, such as simple filament lighting or a heating element with no electronics.
Type A AC plus pulsating DC residual current The minimum for general purpose domestic circuits including socket outlets. This is what most RCBOs you buy today should be.
Type F As Type A plus mixed frequency residual current Circuits feeding variable speed drives and some appliances such as modern washing machines.
Type B As Type F plus smooth DC residual current EV charging, solar PV and other applications where smooth DC can appear.
Check the marking before you fit it. The RCD type is printed on the front of the device as a small symbol next to the rating. If you are replacing like for like in an older board, do not assume the existing device was the right type. Amendment 2 came into force on 27 September 2022 and a great deal of Type AC stock was in service before that.

Choosing the right device: curve and breaking capacity

Two more specifications decide which product you actually order, and both are on the front of the device.

Curve type: how fast it trips on a surge

The letter before the current rating, such as the B in B32, is the magnetic trip curve. It describes how many times the rated current has to flow before the device trips instantly, and it is defined in BS EN 60898-1.

Curve Instantaneous trip range Typical use
Type B 3 to 5 times In The standard choice for domestic lighting and socket circuits. Low inrush, so it can be set sensitive.
Type C 5 to 10 times In Circuits with moderate inrush such as banks of fluorescent or LED lighting, small motors and transformers.
Type D 10 to 20 times In High inrush loads such as large motors, welders and X ray equipment. Rarely appropriate in a house.
Do not fix nuisance tripping by moving up a curve. If a B curve device trips on inrush, the correct fix is usually to check the load and the circuit design, not to fit a C curve and lose sensitivity. A higher curve raises the fault current needed for instant disconnection, which can compromise the disconnection times the circuit was designed around.

Breaking capacity: 6 kA or 10 kA

Breaking capacity is the highest fault current the device can interrupt safely. It has nothing to do with the load and everything to do with how close you are to the supply transformer.

Rating What it means When to specify it
6 kA Interrupts a prospective fault current up to 6,000 A Adequate for most domestic installations, where the prospective fault current at the origin is typically well below this.
10 kA Interrupts a prospective fault current up to 10,000 A Commercial and industrial work, properties close to a substation, and any installation where the measured prospective fault current exceeds 6 kA.

The prospective fault current is measured, not guessed. It appears on the Electrical Installation Certificate, and it is the number that decides whether 6 kA devices are acceptable.

When an MCB is still the right choice

RCBOs are not automatically correct for everything, and specifying them everywhere is a way of spending money without buying safety.

  • Circuits that must not be RCD protected. A fire alarm panel or certain security systems may be specified without RCD protection so that an unrelated earth fault cannot disable them.
  • Where an upstream RCD already provides protection. If the circuit sits behind a suitable RCD, adding a second residual current device in series can create discrimination problems rather than solving them.
  • Commercial and industrial distribution. Where circuits feed fixed equipment rather than socket outlets, and the risk assessment supports it.
  • Board space and budget on a limited alteration. Adding one circuit to an existing split load board is a different decision from specifying a new installation.
A note on discrimination. Putting a 30 mA RCBO behind a 30 mA RCD does not give you two layers of protection. It gives you two devices that will both trip on the same fault, with no way to predict which. If selectivity matters, that is a design decision involving time delayed or S type devices, not something to improvise at the board.

Choosing between products

  1. Confirm the RCD type. Type A as a minimum for general domestic circuits. Type B where EV charging or solar is involved.
  2. Confirm the breaking capacity. 6 kA for most domestic work, 10 kA where the measured prospective fault current or the specification demands it.
  3. Pick the curve. B for standard domestic lighting and power. C only where inrush genuinely justifies it.
  4. Match the manufacturer to the board. Devices must be the type verified by the consumer unit manufacturer for that enclosure. Mixing brands in a board is not a like for like swap.
  5. Check the module width. Full width and compact or mini RCBOs differ. On a full board, a compact device can be the difference between fitting and not fitting.
Do not mix manufacturers in a consumer unit. A consumer unit is type tested as an assembly. Fitting another manufacturer's device into it can invalidate that verification and the manufacturer's warranty, even where the device physically clips onto the rail.

What we stock

Our range is organised by brand and breaking capacity, which are the two things you need to match when ordering.

Schneider

Easy9 6 kA RCBOs and 6 kA MCBs, plus the KQ range formerly sold as Square D.

FuseBox

6 kA RCBOs, 10 kA RCBOs and 6 kA MCB devices, including compact mini RCBOs for tight boards.

Specifying a full board rather than a single device? Browse our consumer units and wider circuit protection range. Single phase and three phase options are available across most brands, and we supply trade, councils, end users and government bodies.

Frequently asked questions

What is the difference between an RCBO and an MCB?

An MCB provides overcurrent protection only, meaning overload and short circuit. An RCBO does the same and adds residual current detection, so it also disconnects when current leaks to earth. In practical terms an MCB protects the cable, while an RCBO protects the cable and provides additional protection against electric shock at 30 mA.

Is an RCBO better than an MCB?

For domestic circuits, generally yes, but for a reason people often miss. Both an RCBO board and a split load board with RCDs can meet the 30 mA requirement. The difference is Regulation 314.1, which requires the installation to be divided so a single fault causes minimum inconvenience. With RCBOs one fault takes out one circuit. With a shared RCD it takes out everything behind that RCD.

Can I replace an MCB with an RCBO?

Often yes, but it is not always a straight swap. The RCBO must be the type verified by the consumer unit manufacturer for that board, it may occupy more module width, and it needs its neutral connecting to the device rather than the neutral bar. This is work that should be done by a competent person and tested, and replacing a consumer unit outright is notifiable under Part P.

Do all socket outlets need a 30 mA RCD?

In effect, in a house, yes. BS 7671 Regulation 411.3.3 requires 30 mA additional protection for socket outlets rated up to 32 A. There is an exception for certain locations where a documented risk assessment carried out with a skilled person determines it is not necessary, and that assessment must be supplied with the installation certificate. The requirement does not apply to socket outlets rated above 32 A.

What is the difference between Type AC and Type A RCBOs?

Type AC detects sinusoidal AC residual current only. Type A also detects pulsating DC, which modern electronics produce. Under Regulation 531.3.3, Type AC devices are only to be used to serve fixed equipment where the load is known to contain no DC components. Type A is the minimum for general purpose domestic circuits including socket outlets.

Should I buy 6 kA or 10 kA devices?

6 kA is adequate for most domestic installations. 10 kA is specified for commercial and industrial work, properties near a substation, and anywhere the measured prospective fault current exceeds 6 kA. That figure is measured during testing and recorded on the Electrical Installation Certificate, so it is a number to look up rather than estimate.

What does the B in B32 mean?

It is the magnetic trip curve. Type B trips instantly at 3 to 5 times the rated current, Type C at 5 to 10 times, and Type D at 10 to 20 times, as defined in BS EN 60898-1. The 32 is the rated current in amps. Type B is the normal choice for domestic lighting and socket circuits.

Why does my RCD keep tripping when nothing seems wrong?

Frequently because several circuits share it. Every appliance has a small standing earth leakage, and those leakages add together on a shared RCD until the total approaches the trip threshold. Nothing is faulty in isolation, but the sum is enough to trip. Moving circuits onto individual RCBOs is the usual fix, because each device then sees only its own circuit's leakage.

Can I mix brands of RCBO in one consumer unit?

No. A consumer unit is type tested as a complete assembly with specific devices. Fitting another manufacturer's device can invalidate that verification and the warranty, even when it physically fits the rail. Order the device that matches the board.

Sources & references

  1. IET, Wiring Matters issue 91, “Mythbusters 8: socket-outlets must be protected by a 30 mA RCD”, electrical.theiet.org. Wording of Regulation 411.3.3, the documented risk assessment exception, and the 32 A ceiling.
  2. IET, Wiring Matters issue 91, Changes to RCD testing in BS 7671:2018+A2:2022. Regulation 531.3.3 on Type AC devices and the 300 ms maximum operating time for general non-delay RCDs at rated residual current.
  3. BS 7671:2018+A2:2022, Requirements for Electrical Installations, IET Wiring Regulations. Regulation 314.1 on division of the installation, Regulation 411.3.3 on additional protection for socket outlets, and Regulation 411.3.4 on AC final circuits supplying luminaires in domestic premises. Amendment 2 came into effect on 27 September 2022.
  4. BS EN 60898-1, Circuit breakers for overcurrent protection for household and similar installations. Instantaneous tripping ranges for Type B, C and D characteristics.
Disclaimer: This article provides general information for trade and informed buyers and is not a substitute for design or installation advice. Device selection depends on the specific installation, its measured characteristics and the applicable regulations. Always consult a competent person and refer to the current edition of BS 7671.
Previous article NEW @westbasedirect.com: Knightsbridge Tri-CCT, IP65, 5W Fire-Rated LED Downlight
Next article FuseBox TPN Range launches at westbasedirect.com

Leave a comment

Comments must be approved before appearing

* Required fields

Compare products

{"one"=>"Select 2 or 3 items to compare", "other"=>"{{ count }} of 3 items selected"}

Select first item to compare

Select second item to compare

Select third item to compare

Compare